RenewOps / Research / EC-WP-1101
The Board That Deleted Its Own Alarms
Alarm management as an information system — load, priority, latching, and the monitor that stops.
EC-WP-1101 in the Monitoring Truth & Fleet Reconciliation Series37 pagesRob Smith, Energy Compliance, Inc.
Seven failure modes in a live alarm subsystem, each with the arithmetic that exposes it. From 7,839 rows on the board to 1,175. From 17 unrendered Critical alarms to 32 rendered. From a suppression rate reported as 14.2% to a measured 80.9%. An analysis of what an alarm system is actually doing to the attention of the people who watch it.
Contents
- What an alarm is supposed to be
- The board that deleted its own alarms
- Load, suppression, and the arithmetic of an operator's burden
- Priority resolution, and who is allowed to decide
- States are not conditions
- Key stability, latching, and why acknowledgement can stop meaning anything
- The monitor that stops
- Ten questions for your own alarm system